| Communication |
DeviceNet |
| Visualization |
none |
| CPU |
16 bits |
| Programming languages per IEC 61131-3 |
Instruction List (IL) Ladder Diagram (LD) Function Block Diagram (FBD), Continuous Function Chart (CFC) Structured Text (ST) Sequential Function Chart (SFC) |
| Programming environment |
WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
| Configuration options |
EDS device description file WAGO-I/O-CHECK |
| Cycle time |
< 3 ms for 1000 bit instructions/ 256 digital I/O |
| Baud rate |
500 kBd (125 kBd, 250 kBd, 500 kBd) |
| Bus segment length (max.) |
500 m |
| Transmission medium (communication/fieldbus) |
Shielded Cu cable; Remote bus cable: 2 x 0.82 mm² + 2 x 1.7 mm²; Drop cable: 2 x 0.2 mm² + 2 x 0.32 mm² |
| Number of fieldbus nodes on master (max.) |
64 |
| Number of I/O points |
6,000 |
| Program memory |
128 KB |
| Data memory |
64 KB |
| Non-volatile software memory |
8 |
| Memory for fieldbus input variables (max.) |
512Byte |
| Memory for fieldbus output variables (max.) |
512Byte |
| Number of modules per node (max.) |
64 |
| Input and output process image (fieldbus) max. |
1024 bytes/1024 bytes |
| DeviceNet features |
Polled I/O message connection Strobed I/O message connection Change of state Cyclic message connection UCMM using function blocks DeviceNet master can be programmed |
| Indicators |
LED (OVERF) red: device error; LED (RUN) green: Device status; LED (BUS OFF) red: Network error ; LED (CONNECT) green: Network status; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply |
| Supply voltage (system) |
24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection) |
| Input current via DeviceNet interface at 11 V |
120mA |
| Input current (typ.) at nominal load (24 V) |
500mA |
| Power supply efficiency (typ.) at nominal load (24 V) |
87% |
| Current consumption (5 V system supply) |
350mA |
| Total current (system supply) |
1,650mA |
| Supply voltage (field) |
24 VDC (-25 … +30 %); via power jumper contacts |
| Current carrying capacity (power jumper contacts) |
10A |
| Number of outgoing power jumper contacts |
3 |
| Isolation |
500 V system/field |