DP / CAN Coupler CANopen® + Layer 2
On the PROFIBUS-DP, the DP/CAN coupler is a normal participant.
The I/O data of the CANopen® participants is shown in the PROFIBUS in a transparent and freely configurable manner.
The DP/CAN coupler is integrated in the hardware configurator with a GSD file and can be completely configured there. Additional tools are not necessary.
On PROFIBUS, all standard transfer rates up to 12 Mbps are supported
General information
- Dimensions (DxWxH) 114 x 18 x 108 mm
- Weight Approx. 110 g
- Status indicator 3 LEDs
- Voltage supply 24 V DC, 18–30 V DC
- Current draw typ. 180 mA with DC 24 V
PROFIBUS interface
- Number 2
- Protocol max. 12 Mbps, autom. detection
- Transmission rate PROFIBUS-DP
- I/O image size max. 240 bytes of input / 240 bytes of output data
- Connection SUB-D female connector, 9-pin
CAN interface
- Number 1
- Type ISO/DIN 11898-2 CAN High-speed physical layer
- Transmission rate 10 kbps ... 1 Mbps
- Protocol CANopen® master CAN 2.0A (11 bit)
- Connection Terminal 3-pin
- TPDOs 4
- RPDOs 4
- Features Sync timer
Ambient conditions
- Ambient temperature -25 °C ... +70°C
- Transport and storage temperature -40 °C … +75 °C
- Relative air humidity 95 % r H without condensation
- Pollution degree 2
- Protection rating IP20
- Certifications CE
CE