PROFINET Coupler DP / PN
With the new DP/PN Coupler, a simple and uncomplicated connection of PROFIBUS to PROFINET is possible. It allows data transfer between a PROFIBUS master and a PROFINET controller. The maximum size of the transmitted data is 244 bytes of input data and 244 bytes of output data. The DP/PN Coupler is projected via a GSD file on the PROFIBUS side and a GSDML file on the PROFINET side. No additional configuration software is necessary.
General information
- Dimensions (DxWxH)32.5 x 58.5 x 76 mm
- Weightapprox. 135 g
PROFINET interface (X1)
- Number 1
- Connection 2x RJ45, integrated switch
- Protocol PROFINET IO Device as defined in IEC 61158-6-10
- Transmission rate 100 Mbps full duplex
- Features
- Media Redundancy Protocol (MRP)
- automatic addressing
- topology detection (LLDP, DCP)
- diagnosis alarm
- PROFINET conformance class B
PROFIBUS interface
- Protocol PROFIBUS-DP
- Connection 9-pin D-sub female connector
- Transmission rate max. 12 Mbps, autom. detection
- I/O image size max. 244 bytes of input / 244 bytes of output data
Status indicator
- Function status 9 LEDs
- Ethernet status 4 LEDs
Power supply
- Operating voltage 24 V DC (18 ... 28 V DC)
- Current draw max. 160 mA
- Power dissipationmax. 3.9 W
Ambient conditions
- Ambient temperature0 °C to 60 °C
- Transport and storage temperature-20 °C to 80 °C
- Protection rating IP 20
- Certifications CE, UL
CE
UL
- UL UL 61010-1 / UL 61010-2-201
- Voltage supply DC 24 V (18 ... 28 VDC, SELV and limited energy circuit)
- Pollution degree 2
- Altitude Up to 2000m
- Temperature cable rating 87 °C