Input module analog for 300s 8x I, U, R
All inputs can be programmed either as voltage or current inputs for Pt100/Ni100 sensors and resistors, freely selectable in their combination.
The signal lines are connected to the corresponding front connectors and can be marked in the label field.
The modules can be fully parameterized with the hardware configurator of the programming software. A hardware configuration is not necessary (no measuring range module).
General information
- Dimensions (DxWxH) 116 x 40 x 125 mm
- Weight Approx. 220g
- Power dissipation (nominal operation) ca. 0.8 W
- Front connectors 40-pin
Measuring ranges
- Voltage ±50 mV, ±500 mV, ±1 V, ±5 V, ±10V, 1 ... 5V, 0 ... 10 V
- Current ±20 mA, 0 ... 20 mA, 4 ... 20 mA
- Resistance 0 ... 6 kΩ, 0 ... 600 Ω
- Resistance thermometer (standard and climate) Pt100, Ni100, Ni1000, LG-Ni1000
Basic error limit at 25 °C
- Voltage input ±0.4 %
- Current input ±0.4 %
- Resistance ±0.4 %
- Resistance thermometer ± 0.8 K Pt100 standard, ±1 K
Operational error limit in the entire temperature range
- Voltage input ±0.6 %
- Current input ±0.6 %
- Resistance ±0.6 %
- Resistance thermometer ±1 K, Pt100, Ni100, standard ±1.2 K
Voltage supply
- Voltage supply 5 V DC via backplane bus
- Current draw Typ. 160 mA at 5 V (from backplane bus)
Ambient conditions
- Ambient temperature 0 °C … +60 °C
- Transport and storage temperature -25 °C … +75 °C
- Pollution degree 2
- Protection rating IP20
- Certifications CE
CE